The maximum reactive power generation of a generator is limited due to:-
1. over heating of the rotor
2. stability limit of the machine
3. thermal consideration
4. both (1) & (2)

1 Answer

0 votes
by (106k points)
selected by
 
Best answer
Correct Answer - Option 1 : over heating of the rotor

Capability curve of synchronous generator:

  • The Capability Curve of a Synchronous Generator defines a boundary within which the machine can operate safely.
  • For an applied shaft power, the reactive power output of a generator is limited by either field current or heating of armature winding
  • Thermal capabilities impose limitations on the synchronous generator reactive power capability.
     

The limitation of operation is restricted to the following:

  • The MVA loading should not exceed the generator rating, this limit is determined by the armature of the stator heating by the armature current.
  • The MW loading should not exceed the rating of the prime mover.
  • The field current should not be allowed to exceed a specified value determined by the heating of the field.
  • For steady-state or stable operation, the load angle δ must be less than 90 degrees.

Welcome to Sarthaks eConnect: A unique platform where students can interact with teachers/experts/students to get solutions to their queries. Students (upto class 10+2) preparing for All Government Exams, CBSE Board Exam, ICSE Board Exam, State Board Exam, JEE (Mains+Advance) and NEET can ask questions from any subject and get quick answers by subject teachers/ experts/mentors/students.