If a transformer is designed for maximum efficiency at rated current and voltage, the full-load copper loss will be
1. much less than the core loss
2. much greater than the core loss
3. equal to the core loss
4. Not definable by these given parameters

1 Answer

0 votes
by (101k points)
selected by
 
Best answer
Correct Answer - Option 3 : equal to the core loss

Concept:

If the maximum efficiency of the transformer occurs at 'k' times of the full load, then:

\(k=\sqrt{\frac{P_i}{(P_{cu})_{fl}}}\)   ---(1)

Where:

Pi = Core iron loss

(Pcu)fl = Full load copper loss

The maximum efficiency occurs at rated current and voltage.

∴ k = 1

Analysis:

Putting k = 1 in the Equation (1), we can write:

\(1=\sqrt{\frac{P_i}{(P_{cu})_{fl}}}\)

∴ Pi = (Pcu)fl

∴ The Full load copper loss will be equal to the core loss.

Welcome to Sarthaks eConnect: A unique platform where students can interact with teachers/experts/students to get solutions to their queries. Students (upto class 10+2) preparing for All Government Exams, CBSE Board Exam, ICSE Board Exam, State Board Exam, JEE (Mains+Advance) and NEET can ask questions from any subject and get quick answers by subject teachers/ experts/mentors/students.