Use app×
Join Bloom Tuition
One on One Online Tuition
JEE MAIN 2025 Foundation Course
NEET 2025 Foundation Course
CLASS 12 FOUNDATION COURSE
CLASS 10 FOUNDATION COURSE
CLASS 9 FOUNDATION COURSE
CLASS 8 FOUNDATION COURSE
0 votes
596 views
in General by (108k points)
closed by
The voltage regulation of a transformer having 2% resistance and 5% reactance at full load, 0.8 pf lagging is
1. 4.6%
2. -4.6%
3. -1.4%
4. 6.4%

1 Answer

0 votes
by (101k points)
selected by
 
Best answer
Correct Answer - Option 1 : 4.6%

Concept:

In transformer voltage regulation is given by,

Voltage regulation = x (Rpu cosθ ± Xpu sinθ)

Where x = fraction of load

Rpu = resistance in pu (we can use % resistive drop in fraction)

Xpu = reactance in pu (we can use % reactive drop in fraction)

+ for lagging load

– for leading load

Calculation:

Given that, transformer is working at 0.8 lagging power factor at full load

⇒ cos θ = 0.8, sin θ = 0.6

x = 1

Rpu = 2%

Xpu = 5%

%V.R. = 1 × (2 × 0.8 + 5 × 0.6) = 4.6%

Welcome to Sarthaks eConnect: A unique platform where students can interact with teachers/experts/students to get solutions to their queries. Students (upto class 10+2) preparing for All Government Exams, CBSE Board Exam, ICSE Board Exam, State Board Exam, JEE (Mains+Advance) and NEET can ask questions from any subject and get quick answers by subject teachers/ experts/mentors/students.

Categories

...