The magnitude of three-phase fault currents at buses A and B of a power system are \(10\;pu\) and \(8\;pu\), respectively. Neglect all resistances in the system and consider the pre-fault system to be unloaded. The pre-fault voltage at all buses in the system \(1.0\;pu\) is . The voltage magnitude at bus B during a three-phase fault at bus A is \(0.8\;pu\). The voltage magnitude at bus A during a three-phase fault at bus B, in \(pu\), is ________.

1 Answer

0 votes
by (152k points)
selected by
 
Best answer

Voltage at bus B after 3 – phase fault at A  \(= 0.8\;p.u.\)

\(\begin{array}{l} {V_B}\; = \;V\left( {prefault} \right)\;-\;{Z_{12}}\; \times \;{I_{f\left( B \right)}}\\ 0.8\; = \;1.0\;-\;{Z_{12}}\; \times \;10\\ {Z_{12}}\; = \;0.02\;p.u.\\ {V_A}\; = \;1.0\;-\;\left( {0.02\; \times \;8} \right)\\ {V_A}\; = \;0.84\;p.u \end{array}\)

Note:

For the voltage magnitude at bus B during a three-phase fault at bus A. So we use fault current of bus A

For the voltage magnitude at bus A during a three-phase fault at bus B. So we use fault current of bus B

Welcome to Sarthaks eConnect: A unique platform where students can interact with teachers/experts/students to get solutions to their queries. Students (upto class 10+2) preparing for All Government Exams, CBSE Board Exam, ICSE Board Exam, State Board Exam, JEE (Mains+Advance) and NEET can ask questions from any subject and get quick answers by subject teachers/ experts/mentors/students.