According to IE rules for service connection for low and medium voltage line, the height of service line conductors erected across a street must NOT be less than:
1. 5.490 m
2. 5.975 m
3. 6.10 m
4. 5.18 m

1 Answer

0 votes
by (30.0k points)
selected by
 
Best answer
Correct Answer - Option 2 : 5.975 m

Clearance above ground at the lowest Conductor:

Voltage Level Description Distance
Low & Medium Voltage
Across a street
5.975 m
High Voltage 6.1 m
Low & Medium Voltage
Along a street
5.5 m
High Voltage 5.8 m
Low & Medium Voltage
Elsewhere than along or across any street
4 m
High Voltage 5.2 m
33 kV & EHV Clearance above ground (+0.3 m for every 33 kV) Min 5.2 m

Welcome to Sarthaks eConnect: A unique platform where students can interact with teachers/experts/students to get solutions to their queries. Students (upto class 10+2) preparing for All Government Exams, CBSE Board Exam, ICSE Board Exam, State Board Exam, JEE (Mains+Advance) and NEET can ask questions from any subject and get quick answers by subject teachers/ experts/mentors/students.