Correct Answer - Option 2 : 1.35
Concept:
COP of Vapor Absorption Refrigeration Cycle (VARS):
\({\left( {COP} \right)_{VARS}} = \left( {\frac{{{T_G} - {T_0}}}{{{T_G}}}} \right) \cdot \left( {\frac{{{T_E}}}{{{T_0} - {T_E}}}} \right)\)
TG is the generator temperature, TE is the evaporator temperature and T0 is the environment temperature
Calculation:
Given:
TG = 95°C = 368 K, TE = -5°C = 268 K, T0 = 30°C = 303 K.
COP of Vapor Absorption Refrigeration Cycle (VARS):
\({\left( {COP} \right)_{VARS}} = \left( {\frac{{{T_G} - {T_0}}}{{{T_G}}}} \right) \cdot \left( {\frac{{{T_E}}}{{{T_0} - {T_E}}}} \right)\)
\({\left( {COP} \right)_{VARS}} = \left( {\frac{{{368}\; - \;{303}}}{{{368}}}} \right) \cdot \left( {\frac{{{268}}}{{{303}\; - \;{268}}}} \right)=1.352\)