Correct Answer - Option 2 : 4 A
Zero sequence component:
- These component vectors consist of three phases equal in magnitude and with zero phase displacement from each other.
- For the flow of zero sequence current under fault conditions, the ground path is mandatory.
- In-ground overcurrent relay, as the ground is present, zero sequence current can flow easily & the fault can be sensed with the relay.
IRo = IYo = IBo
NOTE: Zero sequence current will flow in the neutral grounded system.
IN = 3IRo
In neutral, zero sequence current flows three times.
Calculations:
IN = 12 A
\(I_{R0}=\dfrac {I_N}{3}=\dfrac{12}{3} = 4 A\)
Zero phase sequence component current in each phase is 4 A