The armature reaction and leakage reactance (drop) of a synchronous generator can be determined -
1. by ZPF test only
2. by OC and SC test
3. by OC and ZPF test
4. by OC test only

1 Answer

0 votes
by (114k points)
selected by
 
Best answer
Correct Answer - Option 3 : by OC and ZPF test

Methods of finding Voltage Regulation in Synchronous Generator:

Synchronous impedance method: In the synchronous impedance method voltage regulation is determined by calculating synchronous impedance Zs.

MMF method: It is also used to determining voltage drop through MMF, but the drops in machine IaXL is voltage quantity and  IaXa  is MMF quantity. Because armature reaction is the reduction of flux which is represented through voltage drop.

Potier Method (ZPF method): In potier method voltage quantities are calculated on a voltage basis and MMF quantities are calculated on an MMF basis.

It separated leakage reactance and armature reactance and named it Potier reactance.

It requires an open circuit, short circuit, and zero power factor tests. But to find only leakage reactance open circuits and zero power factor tests are sufficient.

Welcome to Sarthaks eConnect: A unique platform where students can interact with teachers/experts/students to get solutions to their queries. Students (upto class 10+2) preparing for All Government Exams, CBSE Board Exam, ICSE Board Exam, State Board Exam, JEE (Mains+Advance) and NEET can ask questions from any subject and get quick answers by subject teachers/ experts/mentors/students.