Correct Answer - Option 3 : 0.0050
Concept:
RSHF (Room Sensible Heat Factor): It is defined as sensible heat load divided by total heat load in a room.
RTH = Room Total Heat, RSH = Room Sensible Heat, RLH = Room Latent Heat.
RTH = RSH + RLH ……….(I)
\({\bf{RSHF}} = \frac{{{\bf{RSH}}}}{{{\bf{RTH}}}} \) ..... (II)
RLH = 50 × cmm × (ω1 – ω2) .....(III)
where, cmm is cubic meter per minute i.e., air changes per minute.
ω1, ω2 = specific humidity of the room and supplied air.
Calculation:
Given:
RSHF = 0.75, RTH = 100 kW, Air changes per minute = 100 m3/min ⇒ 100 × 106 cm3/min.
By using equation (II)
\({{RSHF}} = \frac{{{{RSH}}}}{{{{RTH}}}} \)
RSH = 0.75 × 100 kW = 75 kW.
By using equation (I)
RTH = RSH + RLH
RLH = 100 – 75 = 25 kW.
By using equation (III)
RLH = 50 × cmm × (ω1 – ω2)
25 = 50 × 100 × (ω1 - ω2)
(ω1 - ω2) = 0.005
0.01 - ω2 = 0.005
ω2 = 0.05 kg/kg of dry air.