For an air-conditioned space, RTH = 100 kW, RSHF = 0.75, volume flow rate of air is 100 m3/minute and room specific humidity is 0.01 kg/kg of dry air. The specific humidity of supply air in kg/kg of dry air is


1. 0.0100
2. 0.0075
3. 0.0050
4. 0.0025

1 Answer

0 votes
by (239k points)
selected by
 
Best answer
Correct Answer - Option 3 : 0.0050

Concept:

RSHF (Room Sensible Heat Factor): It is defined as sensible heat load divided by total heat load in a room.

RTH = Room Total Heat, RSH = Room Sensible Heat, RLH = Room Latent Heat.

RTH = RSH + RLH ……….(I)

\({\bf{RSHF}} = \frac{{{\bf{RSH}}}}{{{\bf{RTH}}}} \) ..... (II)

RLH = 50 × cmm × (ω1 – ω2) .....(III) 

where, cmm is cubic meter per minute i.e., air changes per minute.

ω1, ω2 = specific humidity of the room and supplied air.

Calculation:

Given:

RSHF = 0.75, RTH = 100 kW, Air changes per minute = 100 m3/min ⇒ 100 × 106 cm3/min.

By using equation (II)

\({{RSHF}} = \frac{{{{RSH}}}}{{{{RTH}}}} \)

RSH = 0.75 × 100 kW = 75 kW.

By using equation (I)

RTH = RSH + RLH

RLH = 100 – 75 = 25 kW.     

By using equation (III)

RLH = 50 × cmm × (ω1 – ω2)

25 = 50 × 100 × (ω1 - ω2)

1 - ω2) = 0.005

0.01 - ω2 = 0.005

ω2 = 0.05 kg/kg of dry air.

Welcome to Sarthaks eConnect: A unique platform where students can interact with teachers/experts/students to get solutions to their queries. Students (upto class 10+2) preparing for All Government Exams, CBSE Board Exam, ICSE Board Exam, State Board Exam, JEE (Mains+Advance) and NEET can ask questions from any subject and get quick answers by subject teachers/ experts/mentors/students.