For the protection of a delta-star transformer using differential protection scheme, which of the following CT connection is used?
1. Primary Star, Secondary Star
2. Primary Delta, Secondary Star
3. Primary Star, Secondary Delta
4. Primary Delta, Secondary Delta

1 Answer

0 votes
by (121k points)
selected by
 
Best answer
Correct Answer - Option 3 : Primary Star, Secondary Delta

Concept:

The differential relay actually compares between primary current and secondary current of power transformer, if any unbalance found in between primary and secondary currents the relay will actuate and inter trip both the primary and secondary circuit breaker of the transformer.

For differential protection of power transformer, CT s must be connected in star in the delta side of the transformer and in delta in the star side of the transformer.

Application:

The given connection for the transformer is Δ-Y.

The star side must be connected in delta. Therefore, the connection for the CT must be Y-Δ connection.

Therefore, primary of CT must be star and the secondary must be delta.

Welcome to Sarthaks eConnect: A unique platform where students can interact with teachers/experts/students to get solutions to their queries. Students (upto class 10+2) preparing for All Government Exams, CBSE Board Exam, ICSE Board Exam, State Board Exam, JEE (Mains+Advance) and NEET can ask questions from any subject and get quick answers by subject teachers/ experts/mentors/students.