Impedance per phase r + jXL – jXC
XL = 2π x 50 x 0.15 = 47.1Ω
XC = 106/32.37 = 26.54Ω
cosφ = 25/32.37
Lagging, since inductive reactance is dominating.
Phase Current = 400/(25 + j20.56) = 12.357
Line Current = √3 x 12.357 = 21.4amp
Since the power factor is 0.772 lagging,
P = total three phase power = √3VLIL cosφ x 10-3KW
= √3 x 400 x 21.4 x 0.772 x 10-3 = 11.446KW
S = total 3 ph KVA 11.446/0.772 = 14.83KVA
Q = total 3 ph “reactive kilo-volt-amp”
√3 = (S2 - P2)0.50 = 9.43 kVAR lagging