In scott connections, the teaser transformer operates on 0.866 of its rated ________.
1. Inductance
2. Capacitance
3. Reactance
4. Voltage

1 Answer

0 votes
by (239k points)
selected by
 
Best answer
Correct Answer - Option 4 : Voltage

Scott connection:

  • The Scott-T Connection is the method of connecting two single-phase transformers to perform the 3-phase to 2-phase conversion and vice-versa.
  • The two transformers are connected electrically but not magnetically.
  • One of the transformers is called the main transformer, and the other is called the auxiliary or teaser transformer.
  • The main transformer is center-tapped at D and is connected to line B and C of the 3-phase side. It has primary BC and secondary a1a2.
  • The teaser transformer is connected to the line terminal A and the center tapping D. It has primary AD and the secondary b1b2.
  • The identical, interchangeable transformers are used for Scott-T connection in which each transformer has a primary winding of Tp turns and is provided with tapping at 0.289 Tp, 0.5 Tp, and 0.866 Tp.
  • The teaser transformer has the primary voltage rating that is √3/2 or 0.866 of the voltage ratings of the main transformer.

Welcome to Sarthaks eConnect: A unique platform where students can interact with teachers/experts/students to get solutions to their queries. Students (upto class 10+2) preparing for All Government Exams, CBSE Board Exam, ICSE Board Exam, State Board Exam, JEE (Mains+Advance) and NEET can ask questions from any subject and get quick answers by subject teachers/ experts/mentors/students.