It is to observe insulation of bearing 6 & 7 and hydrogen seal assembly. It requires minimum leakage current (<100mA) through bearings and shaft seals to avoid pitting of bearings.
If the leakage current >100mA, clean the insulation provided between bearing pedestal and seal housing with earth.